Environmental conditions
Temperature range: -25 °C/+125 °C – KREG
-25 °C/+130 °C – KREG M20 *1
1) upper limit temperature (insulating body) RTI (electrical) of the UL Yellow Card
Materials
Insulating body: PA, V-2 according to UL94
PA, V-0 according to UL94 – KREG M20 *1
Clamp: CuZn, nickel-plated
Wire protector: CuZn, pre-nickel and tin-plated
Screw: steel, zinc-plated and chromated
1) KREG M20: material halogen-free, GWFI 960 °C, GWIT 775 °C; not yet filed for VDE/UL/CSA approval
Mechanical data
Screw size: M3
Connectable conductors for screw clamp
Section stranded wire: 0.2–4.0 mm² (VDE)
AWG 22–14 (UL, CSA)
Section stranded wire with ferrule: 0.2–2.5 mm² (VDE)
AWG 22–14 (UL, CSA)
Section solid wire: 0.2–4.0 mm² (VDE)
AWG 22–12 (UL)/AWG 22–14 (CSA)
Stripping length: 7.0 ± 0.5 mm
Electrical data (at Tamb 20 °C)
Rated current: 16 A (Tamb 100 °C, VDE), 15 A (UL)
Rated voltage: 250 V AC *1
1) according to IEC 60664/DIN EN 60664, CTI UL classification according to ANSI/UL 746A